Home outlet wiring question - Page 4 - Homesteading Today
You are Unregistered, please register to use all of the features of Homesteading Today!    
Homesteading Today

Go Back   Homesteading Today > General Homesteading Forums > Homesteading Questions


Like Tree30Likes

Reply
 
LinkBack Thread Tools Rate Thread
  #61  
Old 01/28/13, 02:20 PM
arabian knight's Avatar
Miniature Horse lover
 
Join Date: Dec 2005
Location: West Central WI.
Posts: 21,250
All this talk about GFI. And if that house is wired like that I bet there is Not One GFI in the whole place. Heck I only have them in my barn, and outside outlets that I PUT IN. But not one is in this house.
Older places never have them. So this talk about GFI's is pretty much mute when looking at the OP situation. I did add one heavier wire and outlet that is on its own. But No GFI. As I do lots of testing of Commercial Coffee equipment. Its 10ga just incase I want to change it over to 220 IF I want to use it on heavier equipment but so I only run the 1800 watt or so coffee machines and without any trouble.
__________________
Oh my, dishes yet to wash and dry

See My Pictures at
http://smg.photobucket.com/albums/0903/arabianknight/

Last edited by arabian knight; 01/28/13 at 02:29 PM.
Reply With Quote
  #62  
Old 01/28/13, 02:46 PM
aka avdpas77
 
Join Date: Dec 2008
Location: central Missouri
Posts: 3,416
A GFI breaker has two "op amps" in it. It measures the current going out of the "hot" or black wire and compares it with the current that is coming back though the neutral (white) wire. If there is less current coming back than is going out, that means that there must be some current returning to ground in some other way than the neutral (not good) and it trips the breaker.

Last edited by o&itw; 01/28/13 at 02:47 PM. Reason: can't spell
Reply With Quote
  #63  
Old 01/28/13, 03:08 PM
Murphy was an optimist ;)
 
Join Date: Oct 2005
Location: Kentucky
Posts: 21,558
Quote:
Originally Posted by idahodave View Post
If the equipment has a short and is connected to ground (like a washer on a concrete floor) the GFI trips. If it's insulated from ground and you touch it and ground at the same time the GFI trips. So yes it does address the hazard of a hot wire shorted to the case.
Thanks... this makes me a bit more comfortable.
__________________
"Nothing so needs reforming as other peoples habits." Mark Twain
Reply With Quote
  #64  
Old 01/28/13, 03:11 PM
Murphy was an optimist ;)
 
Join Date: Oct 2005
Location: Kentucky
Posts: 21,558
Quote:
Originally Posted by o&itw View Post
A GFI breaker has two "op amps" in it. It measures the current going out of the "hot" or black wire and compares it with the current that is coming back though the neutral (white) wire. If there is less current coming back than is going out, that means that there must be some current returning to ground in some other way than the neutral (not good) and it trips the breaker.
Thank you so very much, this is probably the clearest explanation of their (gfi) function I have ever heard.
Sawmill Jim likes this.
__________________
"Nothing so needs reforming as other peoples habits." Mark Twain
Reply With Quote
  #65  
Old 01/28/13, 03:41 PM
idahodave's Avatar  
Join Date: Jan 2005
Location: SE Idaho
Posts: 532
Quote:
Originally Posted by arabian knight View Post
Older places never have them. So this talk about GFI's is pretty much mute when looking at the OP situation.
No, it's the easiest way to update outlets in an older home. I think the OP will have a problem finding 2 prong outlets and will have to use GFIs to replace his improperly wired 3 prong outlets.
Reply With Quote
  #66  
Old 01/28/13, 03:50 PM
 
Join Date: Dec 2008
Location: Tennessee
Posts: 8,289
Quote:
Originally Posted by GoldenCityMuse View Post
Obviously, you have not been bold enuff!

Or stupid enough one
__________________
Check it Out O added another Plank With O care
http://www.libertyzone.com/Communist...to-Planks.html
Reply With Quote
  #67  
Old 01/28/13, 03:57 PM
Murphy was an optimist ;)
 
Join Date: Oct 2005
Location: Kentucky
Posts: 21,558
Quote:
Originally Posted by idahodave View Post
No, it's the easiest way to update outlets in an older home. I think the OP will have a problem finding 2 prong outlets and will have to use GFIs to replace his improperly wired 3 prong outlets.
With my newly updated education on the function of the gfi, it would make sense to me if the OP were to simply upgrade all of his circuits with gfi breakers at the panel he would be nearly as safe, if not as safe, as he would be by installing all new wiring to have access to the more modern style ground system. Do I have this correct? The reason I am asking this is because I own a couple houses with the "old style" wiring.
__________________
"Nothing so needs reforming as other peoples habits." Mark Twain
Reply With Quote
  #68  
Old 01/28/13, 04:33 PM
idahodave's Avatar  
Join Date: Jan 2005
Location: SE Idaho
Posts: 532
Yes, you can use a breaker panel mounted GFCI if you can find one that fits.

There are some restricitons.

The neutral must not be shared with another circuit. This is because some of the current in the other circuit would travel in both neutrals and cause the GFCI to trip. This could be a problem in EMT (thinwall conduit) where neutrals can be connected together at a junction box. The other commonly found shared neutral is a network where both sides of the line share a common neutral. Sometimes done with split outlets so each side of the outlet is on a different circuit.
Reply With Quote
  #69  
Old 01/28/13, 04:41 PM
Murphy was an optimist ;)
 
Join Date: Oct 2005
Location: Kentucky
Posts: 21,558
Quote:
Originally Posted by idahodave View Post
Yes, you can use a breaker panel mounted GFCI if you can find one that fits.

There are some restricitons.

The neutral must not be shared with another circuit. This is because some of the current in the other circuit would travel in both neutrals and cause the GFCI to trip. This could be a problem in EMT (thinwall conduit) where neutrals can be connected together at a junction box. The other commonly found shared neutral is a network where both sides of the line share a common neutral. Sometimes done with split outlets so each side of the outlet is on a different circuit.
I would be replacing fuse boxes with breaker panels so matching breakers should not be too big a problem. Now sorting out which circuits may be sharing a neutral could be a bit trickier! These houses are old timers and both have had several hands in the wiring over the years. Everything still works, but I was thinking of going through, replacing all the plugs, switches and main panel boxes in order to eliminate basic issues. There is no conduit to deal with, they were both wired with the old two wire cloth covered style romex. and I am pretty sure both have all four circuits... at least thats how many fuses there are in the panels. Complete rewiring would be a tremendous expense that I simply am not capable of at this point.
__________________
"Nothing so needs reforming as other peoples habits." Mark Twain

Last edited by Yvonne's hubby; 01/28/13 at 04:48 PM.
Reply With Quote
  #70  
Old 01/28/13, 05:10 PM
idahodave's Avatar  
Join Date: Jan 2005
Location: SE Idaho
Posts: 532
I'd pull the fuses and then remove one of the Romex feeders. Use an ohmeter and measure resistance from the white wire on the Romex to the common neutral in the panel. If you have a low (few ohms) reading the neutral is shared. You could then pull the other Romex whites off the common point until the reading goes up.

Don't forget the "No Equipment Ground" label at outlets that aren't grounded.
BMCC likes this.
Reply With Quote
  #71  
Old 01/28/13, 05:19 PM
Murphy was an optimist ;)
 
Join Date: Oct 2005
Location: Kentucky
Posts: 21,558
Quote:
Originally Posted by idahodave View Post
I'd pull the fuses and then remove one of the Romex feeders. Use an ohmeter and measure resistance from the white wire on the Romex to the common neutral in the panel. If you have a low (few ohms) reading the neutral is shared. You could then pull the other Romex whites off the common point until the reading goes up.

Don't forget the "No Equipment Ground" label at outlets that aren't grounded.
Thanks Dave.. You have been very helpful!
BMCC likes this.
__________________
"Nothing so needs reforming as other peoples habits." Mark Twain
Reply With Quote
  #72  
Old 01/28/13, 05:53 PM
arabian knight's Avatar
Miniature Horse lover
 
Join Date: Dec 2005
Location: West Central WI.
Posts: 21,250
Quote:
Originally Posted by idahodave View Post
No, it's the easiest way to update outlets in an older home. I think the OP will have a problem finding 2 prong outlets and will have to use GFIs to replace his improperly wired 3 prong outlets.
Yes cause if not that tiny tiny amount that may trickle into the neutral side will TRIP the GFI outlet. They do not take hardly any flow at all. And it trips.
__________________
Oh my, dishes yet to wash and dry

See My Pictures at
http://smg.photobucket.com/albums/0903/arabianknight/
Reply With Quote
Reply



Thread Tools
Rate This Thread
Rate This Thread:

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Wiring Question Williams farm Shop Talk 18 01/25/11 07:26 PM
winxp home question about Music files texastami Computer Questions 20 04/23/07 08:35 AM
87 Gmc 2500 Wiring Question dvcowboy Shop Talk 1 01/09/07 10:57 PM
Doublewide or not ? Randy Dandy Homesteading Questions 27 02/28/05 05:27 AM
wiring question pcdreams Homesteading Questions 12 12/10/03 08:25 PM


All times are GMT -5. The time now is 02:01 PM.
Contact Us - Homesteading Today - Archive - Privacy Statement - Top - ©Carbon Media Group Agriculture